Lines in italics are for the reader, not the crew. If you can, hold up an extension cord while you read. How to read a talk
Printable version with sign-in sheet (PDF)
Read this out loud
Morning, everybody. Today is about the stuff we plug in all day without a thought. Cords, plugs, and the electrical panel on the wall.
The jacket on a cord has one job: keep the electricity inside. When it gets cut or crushed, the electricity has a way out. And the closest way out may be your hand.
Look before you plug in
Washington's rule says cords and plug-in tools get a look before use, every shift. Run your eye down the cord and check the plug. You're looking for cuts in the jacket, spots that look pinched or crushed, loose parts, and bent or missing pins.
That round third pin is the ground. It's there to protect you if something goes wrong inside the tool. So a plug with that pin snapped off is a damaged cord. And no adapter that skips the ground.
If it's damaged
The rule says a damaged cord comes out of service until it's repaired and tested. So don't hang it back up for the next person. Set it aside and tell your supervisor, so it gets fixed right or replaced.
And the way we read it, tape is not a repair. Tape hides the damage. It doesn't fix it.
Somebody always says, "It still works." Sure it does. A damaged cord works just fine, right up until the day it doesn't.
Plugging in
Plug and unplug with dry hands.
If a plug doesn't fit the outlet, don't force it. Ask your supervisor.
And keep cords out of doorways. A door closing on a cord can crush the wires inside, where you can't see it. If you need power somewhere every day and there's no outlet close by, tell your supervisor, so you can work it out together.
The panel
Last thing, the electrical panel. The rule says the space in front of it is not storage. Keep it clear, at least three feet out. No pallets or carts parked in front.
Why? When something goes wrong, somebody has to get to that panel fast. Nobody should have to move a pallet first.
Talk it over
- You grab an extension cord and find a cut in the jacket. What do you do with it?
- What would make it easier for us to keep good cords handy and the space in front of the panel clear, even on our busiest day?
Before you go
Look before you plug in. Damaged cords come out, and tape is not a repair. Dry hands. And keep the panel clear.
Short on time, or no one to lead it? Doc and Red can run this talk for you in the R Safety Hub app.
Get started
Reference (not read aloud). Washington: WAC 296-800-28030(1) (visual inspection of portable cord- and plug-connected equipment and extension cords before use on each work shift, for loose parts, deformed or missing pins, external defects and damage, damage to the outer covering or insulation, and pinched or crushed covering or insulation that might indicate internal damage), (2) (any defective or damaged cord removed from service until repaired and tested), (4)(c) (cords not run through doorways, windows or similar openings), (7) (insulation intact), (8)(b) (continuous lengths without splice or tap), (9) (no wet hands to plug or unplug energized equipment or extension cords), (10)(b) (cords protected from accidental damage such as from sharp corners, projections, and doorways or other pinch points); WAC 296-800-28010(2), (3) (proper mating configuration between plug and receptacle; outlets and plugs will not accept a plug of a different voltage or current rating); WAC 296-800-28027(2)(a), (2)(c) with Table XX, (3)(a) (working space in front of equipment likely to need examination, adjustment, servicing or maintenance while energized: the width of the equipment or thirty inches, whichever is greater; depth not less than Table XX, three feet at 0 to 150 volts to ground and three to four feet at 151 to 600 volts; working space not used for storage); WAC 296-800-28040(2)(c) and its note (exposed metal parts of hand-held and other listed cord- and plug-connected tools grounded; a three-prong plug and grounded system is one way); WAC 296-24-985(1)(b), (1)(c)(ii), (iii), (1)(e)(i) (the same before-use look and removal from service; plugs and receptacles not connected or altered so the ground is broken; adapters that interrupt the equipment grounding connection not used; hands not wet when plugging and unplugging if energized equipment is involved), with WAC 296-24-965(1) (these work-practice sections cover qualified and unqualified persons). Federal: 29 CFR 1910.334(a)(2), (a)(3), (a)(5)(i); 1910.305(g)(1)(iv), (g)(2)(ii); 1910.303(g)(1) and Table S-1 (same substance).