Morning, everybody. Today is about the electrical panels and temporary power boxes on this job. Not for the electricians. For the rest of us, who walk past them, plug into them, and sometimes stack things in front of them.

Only qualified people work on live parts

Only qualified people work on electrical parts that haven't been shut off and locked or tagged out under the lockout steps. If you're not the electrician, you don't open a panel to poke at it, and you don't pull a cover to see what's in there. Nobody reaches blindly into a box or a space that may have live parts.

If a breaker trips, don't keep flipping it back on. The rule says a tripped circuit isn't turned back on until someone has made sure it's safe, and resetting it over and over is not allowed.

A lock or tag on a panel comes off only by the person who put it on, or under their direct supervision. Never yours to pull.

And nobody works so close to a live circuit that they could touch it, unless it's been shut off and grounded, or guarded with insulation or something else that works.

Covers stay on

Panels out where the rest of us can reach them are mounted in cabinets or boxes built for them, with a dead front. No live parts showing from the front. If a cover's off, a door won't close, or you can see wires, stay back and tell your supervisor.

Live parts at fifty volts or more have to be guarded so nobody touches them by accident. Where a panel could get hit by equipment or material, the guard or box has to be strong enough to take it. Out in damp or wet spots, the boxes have to keep water out, and in wet spots they have to be weatherproof.

If a room or fenced area has a sign saying only qualified people may enter, that means you stay out.

On a construction site, open wiring that's needed for the work has to be kept out of reach of people who aren't supposed to be there.

Keep the space in front clear

There has to be room to work in front of a panel. The space in front is at least three feet deep. Depending on the voltage and what's around it, the rule can call for up to four feet. It's at least thirty inches wide, and at least six feet three inches of headroom.

And that space is not storage. No drywall stacked in front of it, no carts parked there, no buckets. And keep cords out of the work space and walkways so nobody trips. When a panel is open in a hallway or open area, that space gets guarded so nobody uses it as a walkway. Walk around it.

Labels

Each disconnect and each circuit is marked to show what it's for, unless that's plain from where it sits. If labels are missing or wrong, tell your supervisor.

Good practice

Not rule text. If a box is hot, buzzing, smells burnt or sparks, stay away, keep others away, and get the supervisor.

Talk it over

  1. Is anything parked or stacked in front of a panel on this job right now?
  2. Who do we call when a cover is missing?

Before you go

Covers on, doors closed, the space in front clear, and only the qualified person goes inside.

Short on time, or no one to lead it? Doc and Red can run this talk for you in the R Safety Hub app.

Get started

Reference (not read aloud). Washington: WAC 296-155-428(1)(a) (no work so close to a power circuit that the employee could contact it unless protected by deenergizing and grounding or effective guarding by insulation or other means), (1)(f) (only qualified persons work on circuit parts not deenergized under WAC 296-155-429(4)); 296-155-449(4) (panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose, dead front, except where accessible only to qualified persons); 296-155-444(8) (disconnecting means and circuits legibly marked for purpose unless evident), (9) (construction site: open wiring made inaccessible to unauthorized personnel), (10)(a) and Table I-1 (600 volts or less: working space depth 3 feet, or 3 1/2 or 4 feet for 151 to 600 volts depending on conditions; at least 30 inches wide; (ii) not used for storage; guarded when normally enclosed live parts are exposed in a passageway or open space; (v) headroom 6 feet 3 inches), (10)(b)(i), (ii) (live parts 50 volts or more guarded against accidental contact; enclosures or guards strong enough where exposed to physical damage). Also 296-155-428(2)(a) (barriers so electrical workspace is not used as a passageway while energized parts are exposed), (11) (no manual reenergizing after a protective device trips until it is determined safe; repetitive manual reclosing prohibited); 296-155-429(4)(e)(iii) (each lock and tag removed by the employee who applied it or under direct supervision; designated qualified person only when that employee is absent, with conditions); 296-155-428(2)(b) (working spaces and walkways kept clear of cords); 296-155-449(5)(a) (enclosures in damp or wet locations keep water out; weatherproof in wet locations); 296-155-444(10)(b)(iii) (warning signs forbidding unqualified persons at entrances to guarded locations with exposed live parts); 296-155-429(4) (lockout, tagging or both). Federal: 29 CFR 1926.403(h) (identification), (i) (600 volts or less: working clearances, clear spaces, headroom, guarding of live parts); 1926.405(d) (panelboards dead front); 1926.416(a)(1) (no work near a circuit unless deenergized and grounded or guarded). "The one box on site that can hurt you without moving," the examples, "tell your supervisor," "guessing which breaker" and the good-practice paragraph are plain explanation or good practice, not rule text.