Morning, everybody. Today is about fire. A building under construction is basically a giant pile of kindling with a roof on it. Lumber, sawdust, cardboard, plastic wrap, foam, fuel, and a bunch of tools that spark or get hot.
So two jobs today. Keep the fire from starting. And if one starts small, know where the extinguisher is and know whether to use it or get out.
Where's the extinguisher?
Quick test. Without looking around, point at the nearest fire extinguisher.
Note for the reader: wait a second, then point to the real one.
Washington's rule says there has to be at least one extinguisher of the right kind for every three thousand square feet of building, and you should never be more than a hundred feet from one. There has to be at least one on every floor. In a building with more than one story, one goes right by a stairway.
And wherever we're using more than five gallons of gas or other flammable liquid, or more than five pounds of flammable gas like propane, there has to be an extinguisher made for liquid fires within fifty feet.
Don't bury it
The rule says the path to firefighting equipment stays clear at all times. An extinguisher behind a stack of drywall and two pallets doesn't count. It's a museum display.
Check it
Extinguishers get a look every month and a maintenance check every year. You can help with the monthly look. Is it there? Is it charged? Is the pin in? Is it damaged? If something's wrong with it, or it's been used, tell your supervisor. The rule says one with a problem comes out of service and gets replaced. A half-empty extinguisher is a gamble. And in winter, anything that can freeze gets protected from freezing.
Using one
If the company gives us extinguishers to use, the rule says we get trained when we're hired and every year after. That training covers the hazards of fighting a fire in its early stage, and the basics of using the extinguisher.
Here's the honest part. An extinguisher is for a small fire, just getting started. If it's bigger than that, spreading, or putting out heavy smoke, you don't fight it. You yell, you get out, and you call 911. That's good practice, not a line from the rule, but it's how people go home.
Know how the alarm works here. The rule says there has to be a way to alert everybody on site and the fire department, and the instructions posted by the phones and entrances.
Keep it from starting
No smoking near anything that's a fire hazard. Fuel, solvents, glue, hot work. Those areas get posted no smoking or open flame.
Fuel goes in approved containers. For five gallons or less, that means an approved metal safety can or a container approved for transport. Not a milk jug. Not a water bottle. And label it, so nobody drinks the gas or puts water in the saw.
Never store fuel in an exit, a stairway or a walkway.
Keep generator and engine exhaust well away from anything that burns.
Outdoors, scrap lumber and other things that burn can't be piled within ten feet of a building. And keep the trash picked up. Sawdust and cardboard don't need much of an invitation.
Talk it over
- Where are the extinguishers on this job, and is anything blocking them right now?
- Where do we keep fuel, and is every can approved and labeled?
Before you go
Know where it is, keep it clear, check it monthly, small fires only. And keep fuel in the right can.