R Safety Hub R Safety Hub Your prescription for a safer workplace

Lockout and Tagout Basics (Construction)

CONSTRUCTION jobs (follows WAC 296-155-429 and 296-155-682(13))

Lines in italics are for the reader, not the crew. How to read a talk

Printable version with sign-in sheet (PDF)

Read this out loud

Morning, everybody. Today is about locks. Not the one on the gang box. The one that keeps a machine or a circuit from coming back to life while your hands are in it.

Here's the picture. You're working on a circuit. You flipped the breaker. Somebody walks by the panel, sees one breaker off, and thinks, "Huh, that's not right," and flips it back on. They were trying to help. That's the whole reason lockout exists. Good intentions don't stop electricity.

What the rule says

When people could touch parts of fixed electric equipment or circuits that have been shut off, those circuits get locked out and tagged. In Washington that means a padlock and a tag at every point where it could be turned back on. The tag says plainly what's being worked on and says don't operate it and don't remove the tag.

The company has to have the steps written down, and you get to see them.

A push button, a selector switch, or an interlock is not a lockout. Those are controls. Controls can be bumped, pressed or overridden. You disconnect it from every source of power, and you lock the disconnect.

Some things store energy even after they're shut off. Electrical gear can hold a charge. Other parts can hold pressure or spring tension. That stored energy has to be released or blocked before anybody calls it safe.

Prove it's dead

Here's the step people skip. Before anything is treated as dead, a qualified person tries the controls to make sure it won't start, and uses a tester to prove there's no voltage. That includes checking for power feeding back from somewhere else.

"I turned it off" is not a test. "I tested it" is a test.

Who takes the lock off

The person who put the lock on takes it off. Or it comes off under their direct supervision. Not your foreman because they're in a hurry. Not your buddy because you went to lunch.

If that person has left the site, the rule allows a designated qualified person to remove it, but only after the company makes sure that person really isn't on site, and makes sure they're told before they come back to work. That's a careful process, not a shortcut.

Before power goes back on, tools and jumpers come out, everybody is warned to stay clear, and somebody looks to make sure everybody is clear.

Not just electrical

Concrete and masonry gear like mixers, pumps, screens and compressors gets the same treatment. No repair or maintenance where it could start up and hurt someone, unless every energy source is locked out and tagged. A mixer drum doesn't care whose arm is inside.

Good practice

A good habit: one person, one lock, one key, and the key stays in your pocket. And with a corded tool, unplug it and keep the plug in sight before you change a blade or a bit. That's good practice, not a quote from the rule.

Somebody's going to say, "It's a two-minute job, I don't need a lock." The lock takes ten seconds. You'll still be done in two minutes and ten.

Talk it over

  1. Do you have your own lock on this job? Where is it right now?
  2. Have you ever walked up to a switch or breaker that was off and not known why?

Before you go

Lock it, tag it, test it. Your lock, your key, your hands.

Short on time, or no one to lead it? Doc and Red can run this talk for you in the R Safety Hub app.

Get started

Reference (not read aloud). Washington: WAC 296-155-429(1)–(4) (lockout and tagging of circuits: padlocks and tags, written procedure, no push buttons or interlocks as the only means, stored energy, verify deenergized, removal by the person who applied it); 296-155-682(13) (concrete and masonry equipment). Chapter 296-803 WAC exempts construction covered by 296-155 (WAC 296-803-100). Federal: 29 CFR 1926.417 (tags; no padlock requirement), 1926.702(j). "One person, one lock, one key" and unplugging corded tools are good practice, not quoted rules.