R Safety Hub R Safety Hub Your prescription for a safer workplace

Propane Cylinders on the Job

Lines in italics are for the reader, not the crew. If you can, read this one next to where the propane is kept. How to read a talk

Printable version with sign-in sheet (PDF)

Read this out loud

Morning, everybody. It's heater season, so propane is all over the job. Torches, heaters, the forklift, the tar kettle. Today is about the cylinders themselves: where they live, how they stand, and how they hook up.

A propane cylinder is a steel bottle full of fuel under pressure. Treat it like that, not like a stool to sit on at lunch.

Where they're kept

Washington's rule is short on this one. Propane does not get stored inside a building. Cylinders waiting to be used get stored outside, in a place that's vented and protected from tampering and from trucks backing into them. And there has to be at least one fire extinguisher at the storage spot, rated twenty B C or better.

Store more than five hundred pounds of propane and the rule adds distance from the building too. Outside, a cylinder stands upright on firm ground or gets firmly secured.

So at the end of the day, the cylinders go back out. Not in the garage, not in the job trailer, not in the stairwell where it's out of the rain.

Inside, while it's in use

The rule does let a cylinder come inside when the work needs it and keeping it outside isn't practical. Then a few things have to be true.

It stands on a firm, level surface, and it's secured upright when it needs to be. No single cylinder inside is bigger than the hundred-pound size. Valves on cylinders holding more than twenty pounds of propane get protected from damage. The hose is listed for propane and rated for the pressure, as short as it can be, not kinked or stretched, and not close enough to the burner to get cooked. Nobody hangs a heater off the valve, the regulator or the hose. And the cylinders, hoses and regulators get placed where they won't get hit or get hot.

A heater stays at least six feet from any propane cylinder, unless it's built to mount on one and keeps its heat off the cylinder. And blower and radiant heaters never point at a cylinder within twenty feet. Running two or more heaters in one open area on the same floor? The rule spaces their cylinders twenty feet apart. Ask your supervisor before you set that up.

A few hard rules

No welding on a propane cylinder. Ever. Washington's rule says it plainly.

Filling small cylinders off a big storage tank happens at least fifty feet from the nearest building. If that's not your job, leave it to the person whose job it is.

Use only approved cylinders, valves, regulators and heaters. Portable heaters used inside have to shut the gas off by themselves if the flame goes out. Only very small heaters on one-pound bottles are let off that rule. And a heater built for another gas doesn't run on propane until it's been converted and tested for it.

If you smell it

That rotten egg smell means gas. Good practice: no flames, no switches, close the cylinder valve if you can do it safely, get people back, and tell your supervisor. Don't go hunting for the leak with a lighter. Somebody always jokes about that one. It's only funny until it isn't.

Talk it over

  1. Where do our cylinders spend the night, and where's the extinguisher?
  2. What would make it easier to get the cylinders back outside at the end of the day?

Before you go

Stored outside, standing firm, hoses short and safe, heaters back six feet, and never a weld on the bottle.

Short on time, or no one to lead it? Doc and Red can run this talk for you in the R Safety Hub app.

Get started

Reference (not read aloud). Washington: WAC 296-155-275(7) (outside, upright on firm foundations or otherwise firmly secured); (1)(a) (approved containers, valves, connectors, regulators); (2) (welding prohibited on containers); (5)(b) (filling portable containers from storage containers not less than 50 feet from the nearest building); (6)(a) (approved appliances); (8)(l), (n), (o) (inside: individual containers no more than 245 lb water capacity; heater-container units on the same unpartitioned floor separated 20 feet; manifold limits); (8)(a) (containers inside only when operational needs make it necessary and outside is impractical), (e) (valves protected on containers over 50 lb water capacity, nominal 20 lb LP-gas), (g) (hose rated for LP-gas, as short as practical, no kinking or straining, not so close to a burner as to be damaged by heat), (h) (portable heaters shut off gas on flame failure; small-heater note), (i) (container valves, connectors, regulators, manifolds, piping and tubing not used as structural supports for heaters), (j) (located to minimize exposure to high temperatures or physical damage), (k) (firm, substantially level surface; secured upright when necessary), (m) (heaters at least 6 feet from any LP-gas container, except heaters designed for attachment; blower and radiant heaters not directed toward any container within 20 feet); (10) (no LPG storage within buildings); (11)(b) (outside storage ventilated enclosure or otherwise protected against tampering or vehicle damage), (11)(a) Table D-3 (500 lb or less, 0 feet; more than that, 10 to 25 feet from buildings); (12) (at least one approved portable extinguisher rated not less than 20-B:C at storage locations). (6)(b) (appliance made for another gas used with LP-gas only after conversion and testing). Federal: 29 CFR 1926.153(b) (welding prohibited on containers; federal (m)(4) allows field welding on maker-applied saddle plates or brackets of some storage containers; Washington's section has no such exception), (j) (storage within buildings prohibited), (k). The rule also covers relief valves, excess flow valves, manifolds and larger systems; the talk keeps to what a crew handles. "Not like a stool to sit on," "not in the garage, the trailer or the stairwell," "if that's not your job, leave it," "ask your supervisor before you set that up," "only very small heaters on one-pound bottles" (our plain wording of the (8)(h) note: under 7,500 BTU per hour on containers of 2.5 lb water capacity or less), and the whole "If you smell it" part (rotten egg smell; no flames or switches; close the valve if safe; get back; tell your supervisor; no lighter) are plain explanation or good practice, not rule text.